© 2026 Lias Industrial | All rights reserved
Phone
+44 (0) 1204 594941
Address
2 John Street, Bromley Cross, Bolton BL7 9BA
Related Products




MBCE-110/230UV - SIL2 certified
UV amplifier for flame scanners. Offers SPDT flame relay and 4-20MA output. Din mountable.
The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a combustion chamber. The module uses Fireye UV scanners to sense flame presence independently or as components in a burner management system.
Many operational characteristics are provided including:
- CE certified
- Self-contained:
MBCE-230UV-1, MBCE-230UV-3
- 230 VAC, 50/60 Hz:
MBCE-110UV-1, MBCE-110UV-2 MBCE-110UV-3, MBCE-110UV-4
- 110 VAC, 50/60 Hz:
Features
- UV scanner compatible
- Flame ON/OFF LED indicator
- 4-20mA output permits direct reading of flame signal strength
- Uses CE certified 11-pin relay base
- Panel surface or DIN-rail mounting
- Flame pull-in threshold adjustment
- Last diget is flame failure response time.
The module provides a cost effective method of monitoring flames using UV sensing. The MBCE-UV is intended for non-permanent operation (burner must be recycled at least once every 24 hours). The MBCE-UV is ideally suited for flame detection in natural gas applications; however, it can be used for flame detection in propane and light fuel oil applications.
Features
• 110 or 230v operation
• For use Flame Scanner UV1AL-6
• Solid state self check for continuous use
• 1 x SPDT Flame on relays
• 1 x SPST Fault relay
• 1 x 4-20mA flame quality output.
• Test jacks
• DIN rail mountable
• Self checking LED
• Flame on LED
• Plug in base
• Approved for SIL2 Installations
• Can be supplied in Zone 1 / 21 enclosures up to 4 per box
• Atex zone 1 Housing
• UV Scanner available in safe or Atex enclosures
Use any scanner:
Part Numbers
| MBCE-110FR-1 | Flame sensor module, FR, 120 VAC, 1 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). (NOT FOR SALE IN US). | |
| MBCE-110FR-1CEX | Flame sensor module, FR, 120 VAC, 1 second FFRT, CE Approved, ATEX / IECEx Exd IIC T6. NOT FOR SALE IN US. | |
| MBCE-110FR-3 | Flame sensor module, FR, 120 VAC, 3 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). (NOT FOR SALE IN US). | |
| MBCE-110FR-3CEX | Flame sensor module, FR, 120 VAC, 3 second FFRT, CE Approved, ATEX / IECEx Exd IIC T6. NOT FOR SALE IN US. | |
| MBCE-110UV-1 | Flame sensor module, UV, 120 VAC, 1 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). For use with UV90L, UV1AL. (NOT FOR SALE IN US). | |
| MBCE-110UV-2 | Flame sensor module, UV, 120 VAC, 2 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). For use with UV90L, UV1AL. (NOT FOR SALE IN US). | |
| MBCE-110UV-3 | Flame sensor module, UV, 120 VAC, 3 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). For use with UV90L, UV1AL. (NOT FOR SALE IN US). | |
| MBCE-110UV-4 | Flame sensor module, UV, 120 VAC, 4 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). For use with UV90L, UV1AL. (NOT FOR SALE IN US). | |
| MBCE-230FR-1 | Flame sensor module, FR, 230 VAC, 1 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). (NOT FOR SALE IN US). | |
| MBCE-230FR-1CEX | Flame sensor module, FR, 230 VAC, 1 second FFRT, CE Approved, ATEX / IECEx Exd IIC T6. NOT FOR SALE IN US | |
| MBCE-230FR-3 | Flame sensor module, FR, 230 VAC, 3 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). (NOT FOR SALE IN US). | |
| MBCE-230FR-3CEX | Flame sensor module, FR, 230 VAC, 3 second FFRT, CE Approved, ATEX / IECEx Exd IIC T6. NOT FOR SALE IN US. | |
| MBCE-230UV-1 | Flame sensor module, UV, 230 VAC, 1 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). For use with UV90L, UV1AL. (NOT FOR SALE IN US). | |
| MBCE-230UV-3 | Flame sensor module, UV, 230 VAC, 3 second FFRT, CE Approved, to be used with stand-alone wiring base (60-2886). For use with UV90L, UV1AL. (NOT FOR SALE IN US). |