FST (Flexible Single Tube)
This Class I igniter is located in a tilting tangentially fired boiler adjacent to the main fuel nozzle.
As an oil igniter, the unique rear atomizer results in a single tube extending to the one piece tip. This design eliminates the need for atomizer maintenance.
As a gas igniter, the gas is directed to the tip through the single flexible tube. Stabilization is maintained by a 7.5 inch swirler which creates a low pressure zone just down stream of the nozzle. Combustion air is provided from the windbox.
Forney’s Flexible Single Tube (FST) Igniter provides multi-fuel, stable and reliable ignition for tangential burners utilizing a flexible design for optimal ignition with tilting nozzles.
Fuel Types: Light - Medium Oil
Markets Served: Corner fired Utility boiler
Product Info
Class 1 warm up and ignition
Capacity up to 11Mw
Air atomised
Designed for tilting burners
Low opacity
Patented protected combustion zone
Flame detection with UV scanner
High energy ignition as standard
Complete stainless steel construction
Available in any length
Diameters from 50mm
Near maintenance-free operation
Up to 99% reliable ignition
Part Numbers
Fuel: | No. 2 Oil or Natural Gas |
BTU Rating: | Oil: 10 – 37 MBTU/hr Gas: 10 – 20 MBTU/hr |
Fuel Pressure: | Oil: 60 – 125 psig Gas: 12 – 25 psig |
Cooling/Combustion Air: | Flow: 40 SCFM Pressure: 6 WC |
Guide Tube OD: | 2.38” |
Mount Tube OD: | 2.88” |
Length: | As Required, up to 8.5’ |
Atomizing Pressure: | 20 psig (Differential over oil pressure) |
Material of Construction: | Guide Tube and Mount Tube, Carbon Steel; Guide Tube Tip and Pilot Area, 304 SST |
Retract Cylinder Air Pressure: (HESI/oil gun) | 60 to 100 psig |
PDF Manuals
Certificates
-
HESI Specifications
Input Voltage: | 120 to 240 VAC, 50/60 Hz |
Input Power: | 120 VAC @ 1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse) |
Output Voltage: | 2000 VDC |
Output Energy: | 12 joules per spark |
Spark Rate: | 3 per second (approximately) |
Duty Cycle: | 50% at temp 0°F to 135°F (-18°C to 57°C) Ambient |